Vent pipes shall be extended separately or combined of full required size not less than 6 inches 152 mm above the roof or fire wall.
Vent pipe height above roof.
All open vent pipes that extend through a roof shall be terminated at least 6 inches 152 mm above the roof and not less than 2 inches 51 mm above the invert of the emergency overflow except that where a roof is to be used for any purpose other than weather protection the vent extensions shall be run at least 7 feet 2134 mm above the roof.
However it needs to be at least six inches above your fixture s flood level to keep from getting wet.
For those stinky vents consider installing odor hog vent caps see image on the roof vents.
A note on the main drain.
Upc i 906 1 and 906 2.
Vent pipes should extend to outdoors above the building roof and should terminate vertically not less than 6 above the roof surface nor more than 24 and must be at least 12 from any vertical surface such as a nearby sidewall.
You are close to your eave and you find that your measurement is 18 feet from peak to penetration on a 4 12 pitch see figure 3.
On a sink that would be either the rim or overflow hole.
The re vent is the only exception since it runs horizontally.
Above the roof plumbing vent height.
Above the roof nor less than one 1 foot.
This may seem suitable since the only purpose for the stack is to provide air and expel sewer gases.
We install our roof vents 6 to 8 inches above the roof line.
Single wall metal pipe shall extend at least 2 feet 610 mm above the highest point where it passes through a roof of a building and at least 2 feet 610 mm higher than any portion of a building within a horizontal distance of 10 feet 3048 mm.
According to the uniform plumbing code the soil pipe or stack pipe shall extend vertically not less than six 6 inches.
Many people mistakenly think that the pipe always has to be 2 feet above the roof peak.
Flagpoling of vents shall be prohibited except where the roof is used for assembly purposes or parking.
Let s look at a couple of examples.